Moulded Case Circuit Breaker Type ENM, 3 pole, 36kA, 32A
Rated current 32A, Short circuit switching capacity (400V) 36kA, Size type 2, Tripping Unit Electronic release for motor protection - Type ENM, Poles 3
Article #: MX232437--
  • Moulded Case Circuit Breaker Type ENM, 3 pole, 36kA, 32A
Article #: MX232437--
Moulded Case Circuit Breaker Type ENM, 3 pole, 36kA, 32A
Rated current 32A, Short circuit switching capacity (400V) 36kA, Size type 2, Tripping Unit Electronic release for motor protection - Type ENM, Poles 3
Quantity:
Sales Unit:
Minimum Quantity:

Other Actions

Schrack-Info

Basic electronic type release for motor protection ENM
The ENM electronic trip unit allows for tighter tolerance trip times.

•Over-load long-time delay protection
Setting current Ir=In x 0.4-0.5-0.6-0.7-0.8-0.9-1.0, OFF
Tripping time Tr (s): 4, 8, 16, Accuracy ±10%
•Short circuit short-time delay protection
Setting current Isd=Ir × 5-6-8-9-10-11-12, OFF, Accuracy ±15%
Tripping time Tsd (ms): 100, Accuracy ±40
•Short circuit instantaneous protection
Setting current Ii=In × 15, Setting current Isdi (within tolerance).
Max. tripping time (ms): 60
•Phase unbalance/Phase failure Iunbal: 30%-40%-50%-60%-70%-80%-90% (Phase failure)-OFF
Max. trip time of phase imbalance (s): 4-6-8-10, Accuracy ±10%
Tripping time of phase failure (s): 0.25, Accuracy ±20%

EAN-Code 9004840893205
Net width 105,00mm
Net height 157,00mm
Net weight 1,85kg
Power loss 2,40W
Min. ambient temperature -40°C
Max. ambient temperature 70°C
Device category circuit breaker
Standard EN 60947-2
Rated current 32A
Rated voltage < 690VAC
Short circuit switching capacity (400V) 36kA
Size type 2
Tripping Unit Electronic release for motor protection - Type ENM
Poles 3
Pollution degree 3
IP Rating IP40
Rated insulation voltage [Ui] 1000V
Rated impulse withsand voltage [Uimp] 8000V
Rated ultimate short-circuit breaking capacity Icu 36kA
Rated service breaking capacity Ics 36kA
AC 380/400/415V 36kA (Icu) / 36kA (Ics)
AC 440V 36kA (Icu) / 36kA (Ics)
AC 500V 25kA (Icu) / 25kA (Ics)
AC 660/690V 6kA (Icu) / 6kA (Ics)
Electrical endurance (Operation cycle) ##
AC 415V, In 6000
AC 690V, In 1500
Manufacturer Schrack
- Sommeroffer
Packaging units 1 pcs